Quick answer
Grids with a lot of solar and wind are harder to keep stable because inverters, unlike spinning generators, add little inertia and little fault current. Frequency then changes faster after a trip, and voltage swings more where the network is weak. Grid-forming inverters and batteries, STATCOMs and synchronous condensers put that support back.
Key takeaways
- Fault level, the current the network can deliver into a short circuit, is the number that tells you how weak your connection is; ask the network operator for it.
- In Great Britain, loss-of-mains protection on site generation was reset from 0.125 to 1 Hz per second, because on a lighter grid an ordinary frequency swing could trip a large amount of healthy generation at once.
- A STATCOM steadies voltage but cannot supply real power or inertia; a synchronous condenser adds inertia and fault current; grid-forming batteries can do part of both.
Coal and gas power stations steadied the grid as a side effect of their heavy spinning generators. Solar, wind and batteries connect through inverters, the power electronics between the plant and the network, and those supply little of that natural support unless they are built or paired to do it. So as the old stations close, frequency moves faster after a trip and voltage swings more at weak points, and the support has to be added back on purpose. If the network operator has told you your connection is weak or asked for voltage support, send us the connection offer and their letter and an engineer will tell you what it means for your site and whether we can help.
This page is for owners and developers of solar, wind and battery sites, and for industrial users who see more voltage dips than they used to. It explains the two quantities that matter, what goes wrong when they fall, and what you can do on your own site. For the equipment itself, see our STATCOM systems.
Inertia: what spinning generators did for free
Inertia is the energy stored in the heavy spinning rotors of conventional generators. Those rotors turn in step with the grid, at 50 Hz in the UK and 60 Hz in the US. When a large generator trips, the others slow down a little, and their stored energy slows the fall in frequency. That buys the seconds that frequency response needs to kick in.
Solar panels have no rotor. Modern wind turbines connect through power electronics, so their spinning blades are decoupled from the grid. Neither adds inertia by itself. As they replace coal and gas plant, there is less inertia on the system and frequency changes faster after a trip.
You can see the effect in the protection settings on site generation. In Great Britain, loss-of-mains protection measures the rate of change of frequency to detect that a site has been cut off from the grid. Many units were set to trip at 0.125 Hz per second. On a lighter grid, an ordinary disturbance could cross that line and trip a large amount of healthy generation at once. So the industry reset the setting to 1 Hz per second, with a half-second delay. If nobody has looked at your site's protection since it was commissioned, check it.
Weak grids and fault level
Fault level is the current the network can deliver into a short circuit at a given point. Think of it as grid strength. A high fault level means a stiff connection where voltage barely moves. A low one means a weak connection, and it is getting more common in places with lots of renewable generation and little conventional plant nearby.
Engineers often turn it into one number, the short circuit ratio: the fault level at the connection divided by the size of the plant connected there. A ratio below about 3 is commonly treated as weak. Below 2, very weak.
At a weak point, three things go wrong:
- Voltage swings more when output changes, so flicker and voltage limits are harder to meet.
- Inverters that rely on following the grid can oscillate with each other or with the network, or trip during a dip.
- Protection may struggle to see a fault, because there is less fault current to detect.
Voltage control matters more than people expect. The expert panel of European grid operators that investigated the April 2025 blackout in Spain and Portugal found many interacting causes, with gaps in voltage and reactive power control near the top of the list. Its president singled out voltage control, rather than the amount of renewable generation, as the lesson.
If you have been asked for a fault level study, voltage support or extra reactive power as a condition of connection, send the offer and the single-line diagram to sales@severnde.co.uk (UK) or sales@renewable-d.com (US), and an engineer will tell you what the requirement means for your site.
What fixes it
Four kinds of equipment put back what the spinning plant used to provide. They do different jobs. Which one you need depends on whether your problem is voltage, frequency or fault current, and on what the network operator has written into your connection offer.
| Fix | What it adds | Where it fits |
|---|---|---|
| STATCOM | Fast reactive power, within about one mains cycle, to hold voltage | Solar and wind farms that must meet voltage and reactive power rules; industrial sites with dips |
| Synchronous condenser | Real inertia and fault current, plus reactive power | Weak areas with little conventional plant nearby |
| Grid-forming inverter or battery | Sets its own voltage and frequency; a form of synthetic inertia | New battery sites; plants at weak connections |
| Battery with fast frequency response | Real power in under a second when frequency falls | Frequency services and site resilience |
A STATCOM is the workhorse for voltage. It is a power electronic device that injects or absorbs reactive power, the part of the supply that holds voltage up. What it cannot do is push real power, so it adds no inertia. Pair it with a battery or supercapacitors and it can do both jobs, which is where some of the newest designs are heading.
Synchronous condensers are big spinning machines with nothing on the shaft. They are the only option here that adds real inertia and fault current. As rotating machines they need more mechanical maintenance than a STATCOM, with bearings, lubrication and cooling to look after, but in a weak area nothing else gives the network quite the same stiffness. Great Britain's first stability tender, in 2020, contracted 12 providers, all synchronous condensers. The second round split its contracts between synchronous condensers and grid-forming batteries.
Grid-forming batteries are newer. Since February 2022 the GB Grid Code has carried a specification for grid-forming capability. It is not mandatory, but it means a battery can be specified and tested to behave more like a spinning machine.
You will also hear the opposite view: newer wind farms have reactive power capability built into the turbines, so they may not need a STATCOM at all. Sometimes that is true. It depends on the cable lengths, the transformers, the low-wind hours and how the site behaves in a fault, which is what a study is for. The comparison is set out in STATCOM vs SVC, and how the equipment works in what a STATCOM is and how it steadies voltage.
Does a microgrid help?
For a critical site, yes. A microgrid that can disconnect and run on its own generation and storage keeps the site going when the wider grid fails. It does nothing for the stability of the grid itself. It also needs the same voltage and frequency control inside its own fence.
What a site owner can do
Most of the useful steps cost little:
- Ask the network operator for the fault level at your connection point, now and after planned changes nearby.
- Check the loss-of-mains and ride-through settings on your generation and batteries.
- Specify grid-forming capability when you buy a new battery or inverter, even where it is not yet required.
- Keep the voltage support you already have working. A STATCOM that has been in service for 15 or 20 years can usually be repaired, upgraded or given new controls for less than a replacement, and much sooner. See STATCOM repair and service.
- If your own site sees voltage dips from the grid, measure them before choosing a fix. Solving voltage sags with a DSTATCOM covers how.
What to send us
- The connection offer or any letter from the network operator about fault level, voltage or reactive power.
- The single-line diagram of the site.
- Nameplate photos of any STATCOM or other voltage support equipment already installed, with its age.
- Power quality data or a trip log, if the site has had disturbances.
What to do next
- Find out how weak your connection is before the network operator tells you.
- Decide whether your problem is voltage, frequency or fault current, because the fix differs.
- Get the equipment you already own tested before you buy new.
Told your connection is weak, or asked for voltage support? We supply, repair and upgrade STATCOMs and run the grid studies networks ask for, from teams in Leicestershire and Wisconsin. Send the connection offer and the single-line diagram, and we will tell you what the requirement means for your site and whether we can help. Send an enquiry, email sales@severnde.co.uk (UK) or sales@renewable-d.com (US), or call +44 116 279 6131 (UK) or +1 414 562 6559 (US).
Frequently asked questions
Why do solar and wind farms reduce grid inertia?
Inertia comes from the heavy spinning rotors of conventional generators, which turn in step with the grid and slow down any change in frequency. Solar panels have no rotor, and modern wind turbines connect through power electronics, so neither adds natural inertia. As they replace conventional plant, frequency moves faster after a large generator or link trips.
What is a weak grid?
A weak grid is a point on the network with a low fault level compared with the size of the plant connected there. Engineers often measure it as the short circuit ratio, and a ratio below about 3 is commonly treated as weak. Voltage swings more at a weak point, and inverters there can oscillate or trip unless they are set up for it.
What is the difference between grid-forming and grid-following inverters?
A grid-following inverter measures the grid's voltage and frequency and injects current to match, so it needs a strong grid to follow. A grid-forming inverter sets its own voltage and frequency, as a spinning generator does, and can respond to a disturbance at once. Grid-forming batteries can provide a form of synthetic inertia and help steady weak areas of the network.
Tags
Working on a project like this?
Talk to our engineering team about your site, your grid connection or your power quality problem.
Get in touch