RED3310S-E UPS, 10 kVA / 10 kW – Internal Batteries

10 kVA / 10 kW three-phase double-conversion online tower UPS for UK and IEC markets, with batteries fitted internally for short autonomy. Efficiency up to 93.5 % (up to 98.0 % in ECO mode); part of the RED3300-E Series.
- True online double conversion with DSP control
- Output power factor 1.0; accepts 100 % unbalanced load
- Efficiency up to 93.5 %, up to 98.0 % in ECO mode
- Internal VRLA batteries — no separate battery cabinet needed
- Wide input range 208–478 Vac, 40–70 Hz; THDi ≤ 3 %
- N+X parallel redundancy, up to 4 units
Overview
The RED3310S-E is the 10 kVA standard (S) model in the RED3300-E Series of three-phase in / three-phase out, true double-conversion online UPS, rated at 380/400/415 Vac for the UK and other IEC markets.
The standard build carries its batteries internally for short autonomy, in a 250 mm-wide tower cabinet.
Battery autonomy, string configuration and battery cabinet selection are sized per project — contact us with your load and runtime requirements. Figures are typical values for reference only; specifications are subject to change without prior notice.
- Rated power
- 10 kW
- Input voltage
- 400 V
- Output voltage
- 400 V
- Battery
- VRLA
- Redundancy
- Parallel · N+1
- Market
- United Kingdom · Global
Specifications
Model
- Model code
- RED3310S-E
- Build
- Standard (S) — batteries fitted internally
- Rated power
- 10 kVA / 10 kW
- Dimensions (W × D × H)
- Chassis 1: 250 × 900 × 868 mm; chassis 2: 250 × 645 × 715 mm
- Weight
- Chassis 1: 129 kg (20 × 9 Ah); chassis 2: 80 kg (16 × 9 Ah)
- Noise
- < 55 dB
- Charging current, max.
- 1.35 A (2.7 A optional)
Electrical
- Topology
- Online double conversion, three-phase in / three-phase out, DSP control
- Nominal input / output voltage
- 380/400/415 Vac, 3-phase + N + PE
- Input voltage range
- 305–478 Vac (full load); 208–478 Vac (50 % load)
- Input frequency range
- 40–70 Hz
- Input power factor
- ≥ 0.99
- Input current distortion (THDi)
- ≤ 3 % (linear load)
- Output power factor
- 1.0 (100 % unbalanced load)
- Voltage regulation
- ±1 %
- Output voltage distortion (THDv)
- ≤ 2 % linear load; ≤ 5 % non-linear load
- Output frequency
- Line mode: ±1 / ±2 / ±4 / ±5 / ±10 % of rated (selectable); battery mode: 50/60 Hz ±0.1 %
- Crest factor
- 3:1
- Bypass voltage range
- Max. 220 V +25 %, 230 V +20 %, 240 V +15 % (lower limits optional); min. −45 % (−20 %, −30 % optional)
- Bypass frequency range
- 50/60 Hz ±10 %
- Overload — AC mode
- ≤ 110 % 60 min; ≤ 125 % 10 min; ≤ 150 % 1 min; > 150 % immediate transfer to bypass
- Overload — battery mode
- ≤ 110 % 10 min; ≤ 125 % 1 min; ≤ 150 % 5 s; > 150 % immediate shutdown
- Efficiency — AC mode
- Up to 93.5 %
- Efficiency — ECO mode
- Up to 98.0 %
- Parallel
- N+X redundancy, up to 4 units
Battery
- Battery type
- VRLA (maintenance-free lead-acid), internal
- Battery configuration
- ±120 Vdc, 20 × 12 V 9 Ah (20 × 7 Ah, 2 × 20 × 7/9 Ah or 3 × 20 × 7/9 Ah optional); chassis 2: ±96 Vdc, 16 × 9 Ah
- Charging current, max.
- 1.35 A (2.7 A optional)
Environmental
- Operating temperature
- 0–40 °C
- Storage temperature
- −25 to 55 °C (without battery)
- Relative humidity
- 0–95 % (non-condensing)
- Altitude
- < 1000 m ASL; derating required above 1000 m
Communications & features
- Interfaces
- USB, RS-232, RS-485, parallel port, dry contact, intelligent slot
- Options
- SNMP card, dry-contact card, battery temperature sensor
- Display
- Segment LCD standard; 2.4" TFT or 7" colour LCD optional
- Functions
- ECO mode, cold start, 50/60 Hz frequency-converter mode, self-test at start-up, intelligent fan speed control
- Protection
- Short circuit, overload, over-temperature, battery overcharge and over-discharge, output low voltage, fan fault alarm
Standards
- Safety
- IEC/EN 62040-1, IEC/EN 62477-1
- EMC
- IEC/EN 62040-2 (IEC 61000-2-2, -4-2, -4-3, -4-4, -4-5, -4-6, -4-8, -4-11)
- Performance
- IEC 62040-3:2021, EN IEC 62040-3:2021
Certification & warranty
Certification
Designed and tested to IEC/EN 62040-1 (safety), IEC/EN 62040-2 (EMC), IEC/EN 62040-3 (performance) and IEC/EN 62477-1. EMC certificates of conformity (EMC Directive 2014/30/EU; EN IEC 62040-2:2018, EN 61000-3-12:2011, EN 61000-3-11:2000) cover the 10–20 kVA models (certificate ES201225018E) and the 30–40 kVA models (certificate ES201225020E). Copies are available on request.
Let's Solve Your Power Challenge.
Send an enquiry to our engineering team. We'll help you identify risks and uncover efficiency opportunities.
Renewable Energy & Drives
5325 S Moorland RdNew Berlin, WI 53151United States
Severn Drives & Energy
Units 2 & 3, Kingsley Business ParkNew Road, Kibworth BeauchampLeicestershire, LE8 0LEUnited Kingdom
Send an enquiry
Fill out the form below and we'll be in touch.