RED33200H-E UPS, 200 kVA / 200 kW – Extended Runtime Model
- IEC/EN 62040-1
- IEC/EN 62477-1
- IEC/EN 62040-2
- IEC 62040-3:2021

200 kVA / 200 kW three-phase double-conversion online tower UPS for UK and IEC markets, supplied without batteries for pairing with external battery cabinets sized to the required autonomy. Efficiency up to 95.5 % (up to 99 % in ECO mode); part of the RED3300-E Series.
- Three-level inverter; efficiency up to 95.5 %, up to 99 % in ECO mode
- Output power factor 1.0; accepts 100 % unbalanced load
- Long-run build for external VRLA or Li-ion, 360–600 Vdc; charger up to 60 A
- Wide input range 138–485 Vac; input PF ≥ 0.99, THDi ≤ 3 %
- Parallel expansion to 6 units with shared battery option; LBS
- Power Walk-In soft start reduces the generator rating required
Overview
The RED33200H-E is the 200 kVA long-run (H) model in the RED3300-E Series of three-phase in / three-phase out, true double-conversion online UPS, rated at 380/400/415 Vac for the UK and other IEC markets.
The long-run build is supplied without batteries and is paired with external VRLA or lithium-ion batteries (360–600 Vdc) sized to the autonomy required.
Battery autonomy, string configuration and battery cabinet selection are sized per project — contact us with your load and runtime requirements. Figures are typical values for reference only; specifications are subject to change without prior notice.
- Rated power
- 200 kW
- Input voltage
- 400 V
- Output voltage
- 400 V
- Battery
- VRLA · Lithium-ion
- Redundancy
- Parallel · N+1
- Market
- United Kingdom · Global
Specifications
Model
- Model code
- RED33200H-E
- Build
- Long-run (H) — supplied without battery
- Rated power
- 200 kVA / 200 kW
- Dimensions (W × D × H)
- 442 × 850 × 1200 mm
- Weight
- 230 kg
- Noise
- < 66 dB
- Charging current, max.
- 60 A
Electrical
- Topology
- Online double conversion, DSP control, three-level inverter
- Nominal input / output voltage
- 380/400/415 Vac, 3-phase + N + PE
- Input voltage range
- 138–305 Vac at 40 % load; 305–485 Vac at 100 % load (phase voltage 80–280 Vac)
- Input power factor
- ≥ 0.99
- Input current distortion (THDi)
- ≤ 3 % (linear load)
- Output power factor
- 1.0 (100 % unbalanced load)
- Voltage regulation
- ±1 %
- Output voltage distortion (THDv)
- ≤ 2 % linear load; ≤ 4 % non-linear load
- Output frequency
- Line mode: synchronised with input (50/60 Hz ±0.1 when input exceeds ±10 %); battery mode: 50/60 Hz ±0.2 %
- Crest factor
- 3:1
- Bypass frequency range
- 50/60 Hz ±10 %
- Overload — inverter mode
- ≤ 110 % 60 min; ≤ 125 % 1 min; > 125 % 1.2 s inverter shutdown
- Overload — bypass mode
- 135 % long term at 30 °C; 125 % long term at 40 °C; > 1000 % for 100 ms
- Efficiency
- AC mode up to 95.5 %; ECO mode up to 99 %
- Parallel
- Up to 6 units, with shared battery option
Battery
- Battery type
- VRLA or lithium-ion, external (not included)
- Battery voltage
- 360–600 Vdc
- Charging current, max.
- 60 A
- Shared battery
- Shared battery option in parallel systems
Environmental
- Operating temperature
- 0–40 °C
- Storage temperature
- −25 to 55 °C (without battery)
- Relative humidity
- 0–95 % (non-condensing)
- Altitude
- < 1000 m ASL; derating required above 1000 m
Communications & features
- Interfaces
- USB, RS-485, RS-232, SNMP and dry-contact card
- Functions
- ECO mode, Power Walk-In soft start, LBS (load bus synchronisation) for dual-bus systems
- Generator
- Generator compatible; Power Walk-In reduces inrush and the generator rating required
Standards
- Safety
- IEC/EN 62040-1, IEC/EN 62477-1
- EMC
- IEC/EN 62040-2 (IEC 61000-2-2, -4-2, -4-3, -4-4, -4-5, -4-6, -4-8, -4-11)
- Performance
- IEC 62040-3:2021, EN IEC 62040-3:2021
Certification & warranty
Certification
- IEC/EN 62040-1
- IEC/EN 62477-1
- IEC/EN 62040-2
- IEC 62040-3:2021
Designed and tested to IEC/EN 62040-1 (safety), IEC/EN 62040-2 (EMC), IEC/EN 62040-3 (performance) and IEC/EN 62477-1. EMC certificates of conformity (EMC Directive 2014/30/EU; EN IEC 62040-2:2018, EN 61000-3-12:2011, EN 61000-3-11:2000) cover the 10–20 kVA models (certificate ES201225018E) and the 30–40 kVA models (certificate ES201225020E). Copies are available on request.
Let's Solve Your Power Challenge.
Send an enquiry to our engineering team. We'll help you identify risks and uncover efficiency opportunities.
Renewable Energy & Drives
5325 S Moorland RdNew Berlin, WI 53151United States
Severn Drives & Energy
Units 2 & 3, Kingsley Business ParkNew Road, Kibworth BeauchampLeicestershire, LE8 0LEUnited Kingdom
Send an enquiry