LOW-VOLTAGE MODULAR UPS

    RED3320S-E UPS, 20 kVA / 20 kW – Internal Batteries

    RED3320S-E20 kVA / 20 kW · 3-phase · 380/400/415 V · internal battery
    RED3320S-E UPS, 20 kVA / 20 kW – Internal Batteries

    20 kVA / 20 kW three-phase double-conversion online tower UPS for UK and IEC markets, with batteries fitted internally for short autonomy. Efficiency up to 94.5 % (up to 98.2 % in ECO mode); part of the RED3300-E Series.

    • True online double conversion with DSP control
    • Output power factor 1.0; accepts 100 % unbalanced load
    • Efficiency up to 94.5 %, up to 98.2 % in ECO mode
    • Internal VRLA batteries — no separate battery cabinet needed
    • Wide input range 208–478 Vac, 40–70 Hz; THDi ≤ 3 %
    • N+X parallel redundancy, up to 4 units

    Overview

    The RED3320S-E is the 20 kVA standard (S) model in the RED3300-E Series of three-phase in / three-phase out, true double-conversion online UPS, rated at 380/400/415 Vac for the UK and other IEC markets.

    The standard build carries its batteries internally for short autonomy, in a 250 mm-wide tower cabinet.

    Battery autonomy, string configuration and battery cabinet selection are sized per project — contact us with your load and runtime requirements. Figures are typical values for reference only; specifications are subject to change without prior notice.

    Rated power
    20 kW
    Input voltage
    400 V
    Output voltage
    400 V
    Battery
    VRLA
    Redundancy
    Parallel · N+1
    Market
    United Kingdom · Global

    Specifications

    Model

    Model code
    RED3320S-E
    Build
    Standard (S) — batteries fitted internally
    Rated power
    20 kVA / 20 kW
    Dimensions (W × D × H)
    250 × 900 × 868 mm
    Weight
    187 kg (2 × 20 × 9 Ah)
    Noise
    < 58 dB
    Charging current, max.
    2.7 A

    Electrical

    Topology
    Online double conversion, three-phase in / three-phase out, DSP control
    Nominal input / output voltage
    380/400/415 Vac, 3-phase + N + PE
    Input voltage range
    305–478 Vac (full load); 208–478 Vac (50 % load)
    Input frequency range
    40–70 Hz
    Input power factor
    ≥ 0.99
    Input current distortion (THDi)
    ≤ 3 % (linear load)
    Output power factor
    1.0 (100 % unbalanced load)
    Voltage regulation
    ±1 %
    Output voltage distortion (THDv)
    ≤ 2 % linear load; ≤ 5 % non-linear load
    Output frequency
    Line mode: ±1 / ±2 / ±4 / ±5 / ±10 % of rated (selectable); battery mode: 50/60 Hz ±0.1 %
    Crest factor
    3:1
    Bypass voltage range
    Max. 220 V +25 %, 230 V +20 %, 240 V +15 % (lower limits optional); min. −45 % (−20 %, −30 % optional)
    Bypass frequency range
    50/60 Hz ±10 %
    Overload — AC mode
    ≤ 110 % 60 min; ≤ 125 % 10 min; ≤ 150 % 1 min; > 150 % immediate transfer to bypass
    Overload — battery mode
    ≤ 110 % 10 min; ≤ 125 % 1 min; ≤ 150 % 5 s; > 150 % immediate shutdown
    Efficiency — AC mode
    Up to 94.5 %
    Efficiency — ECO mode
    Up to 98.2 %
    Parallel
    N+X redundancy, up to 4 units

    Battery

    Battery type
    VRLA (maintenance-free lead-acid), internal
    Battery configuration
    ±120 Vdc, 2 × 20 × 12 V 9 Ah (2 × 20 × 7 Ah or 3 × 20 × 7/9 Ah optional)
    Charging current, max.
    2.7 A

    Environmental

    Operating temperature
    0–40 °C
    Storage temperature
    −25 to 55 °C (without battery)
    Relative humidity
    0–95 % (non-condensing)
    Altitude
    < 1000 m ASL; derating required above 1000 m

    Communications & features

    Interfaces
    USB, RS-232, RS-485, parallel port, dry contact, intelligent slot
    Options
    SNMP card, dry-contact card, battery temperature sensor
    Display
    Segment LCD standard; 2.4" TFT or 7" colour LCD optional
    Functions
    ECO mode, cold start, 50/60 Hz frequency-converter mode, self-test at start-up, intelligent fan speed control
    Protection
    Short circuit, overload, over-temperature, battery overcharge and over-discharge, output low voltage, fan fault alarm

    Standards

    Safety
    IEC/EN 62040-1, IEC/EN 62477-1
    EMC
    IEC/EN 62040-2 (IEC 61000-2-2, -4-2, -4-3, -4-4, -4-5, -4-6, -4-8, -4-11)
    Performance
    IEC 62040-3:2021, EN IEC 62040-3:2021

    Certification & warranty

    Certification

    Designed and tested to IEC/EN 62040-1 (safety), IEC/EN 62040-2 (EMC), IEC/EN 62040-3 (performance) and IEC/EN 62477-1. EMC certificates of conformity (EMC Directive 2014/30/EU; EN IEC 62040-2:2018, EN 61000-3-12:2011, EN 61000-3-11:2000) cover the 10–20 kVA models (certificate ES201225018E) and the 30–40 kVA models (certificate ES201225020E). Copies are available on request.

    GET IN TOUCH

    Let's Solve Your Power Challenge.

    Send an enquiry to our engineering team. We'll help you identify risks and uncover efficiency opportunities.

    North America

    Renewable Energy & Drives

    5325 S Moorland RdNew Berlin, WI 53151United States

    UK & Europe

    Severn Drives & Energy

    Units 2 & 3, Kingsley Business ParkNew Road, Kibworth BeauchampLeicestershire, LE8 0LEUnited Kingdom

    Send an enquiry

    Fill out the form below and we'll be in touch.