LOW-VOLTAGE MODULAR UPS

    RED3350H-E UPS, 50 kVA / 50 kW – Extended Runtime Model

    RED3350H-E50 kVA / 50 kW · 3-phase · 380/400/415 V · long-run, external battery
    RED3350H-E UPS, 50 kVA / 50 kW – Extended Runtime Model

    50 kVA / 50 kW three-phase double-conversion online tower UPS for UK and IEC markets, supplied without batteries for pairing with external battery cabinets sized to the required autonomy. Efficiency up to 95.5 % (up to 99 % in ECO mode); part of the RED3300-E Series.

    • Three-level inverter; efficiency up to 95.5 %, up to 99 % in ECO mode
    • Output power factor 1.0; accepts 100 % unbalanced load
    • Long-run build for external VRLA or Li-ion, 360–600 Vdc; charger up to 20 A
    • Wide input range 138–485 Vac; input PF ≥ 0.99, THDi ≤ 3 %
    • Parallel expansion to 6 units with shared battery option; LBS
    • Power Walk-In soft start reduces the generator rating required

    Overview

    The RED3350H-E is the 50 kVA long-run (H) model in the RED3300-E Series of three-phase in / three-phase out, true double-conversion online UPS, rated at 380/400/415 Vac for the UK and other IEC markets.

    The long-run build is supplied without batteries and is paired with external VRLA or lithium-ion batteries (360–600 Vdc) sized to the autonomy required.

    Battery autonomy, string configuration and battery cabinet selection are sized per project — contact us with your load and runtime requirements. Figures are typical values for reference only; specifications are subject to change without prior notice.

    Rated power
    50 kW
    Input voltage
    400 V
    Output voltage
    400 V
    Battery
    VRLA · Lithium-ion
    Redundancy
    Parallel · N+1
    Market
    United Kingdom · Global

    Specifications

    Model

    Model code
    RED3350H-E
    Build
    Long-run (H) — supplied without battery
    Rated power
    50 kVA / 50 kW
    Dimensions (W × D × H)
    250 × 828 × 868 mm
    Weight
    80 kg
    Noise
    < 55 dB
    Charging current, max.
    20 A

    Electrical

    Topology
    Online double conversion, DSP control, three-level inverter
    Nominal input / output voltage
    380/400/415 Vac, 3-phase + N + PE
    Input voltage range
    138–305 Vac at 40 % load; 305–485 Vac at 100 % load (phase voltage 80–280 Vac)
    Input power factor
    ≥ 0.99
    Input current distortion (THDi)
    ≤ 3 % (linear load)
    Output power factor
    1.0 (100 % unbalanced load)
    Voltage regulation
    ±1 %
    Output voltage distortion (THDv)
    ≤ 2 % linear load; ≤ 4 % non-linear load
    Output frequency
    Line mode: synchronised with input (50/60 Hz ±0.1 when input exceeds ±10 %); battery mode: 50/60 Hz ±0.2 %
    Crest factor
    3:1
    Bypass frequency range
    50/60 Hz ±10 %
    Overload — inverter mode
    ≤ 110 % 60 min; ≤ 125 % 10 min; ≤ 150 % 1 min; > 150 % 1.2 s inverter shutdown
    Overload — bypass mode
    135 % long term at 30 °C; 125 % long term at 40 °C; > 1000 % for 100 ms
    Efficiency
    AC mode up to 95.5 %; ECO mode up to 99 %
    Parallel
    Up to 6 units, with shared battery option

    Battery

    Battery type
    VRLA or lithium-ion, external (not included)
    Battery voltage
    360–600 Vdc
    Charging current, max.
    20 A
    Shared battery
    Shared battery option in parallel systems

    Environmental

    Operating temperature
    0–40 °C
    Storage temperature
    −25 to 55 °C (without battery)
    Relative humidity
    0–95 % (non-condensing)
    Altitude
    < 1000 m ASL; derating required above 1000 m

    Communications & features

    Interfaces
    USB, RS-485, RS-232, SNMP and dry-contact card
    Functions
    ECO mode, Power Walk-In soft start, LBS (load bus synchronisation) for dual-bus systems
    Generator
    Generator compatible; Power Walk-In reduces inrush and the generator rating required

    Standards

    Safety
    IEC/EN 62040-1, IEC/EN 62477-1
    EMC
    IEC/EN 62040-2 (IEC 61000-2-2, -4-2, -4-3, -4-4, -4-5, -4-6, -4-8, -4-11)
    Performance
    IEC 62040-3:2021, EN IEC 62040-3:2021

    Certification & warranty

    Certification

    Designed and tested to IEC/EN 62040-1 (safety), IEC/EN 62040-2 (EMC), IEC/EN 62040-3 (performance) and IEC/EN 62477-1. EMC certificates of conformity (EMC Directive 2014/30/EU; EN IEC 62040-2:2018, EN 61000-3-12:2011, EN 61000-3-11:2000) cover the 10–20 kVA models (certificate ES201225018E) and the 30–40 kVA models (certificate ES201225020E). Copies are available on request.

    GET IN TOUCH

    Let's Solve Your Power Challenge.

    Send an enquiry to our engineering team. We'll help you identify risks and uncover efficiency opportunities.