RED3360S-E UPS, 60 kVA / 60 kW – Internal Batteries
60 kVA / 60 kW three-phase double-conversion online tower UPS for UK and IEC markets, with batteries fitted internally for short autonomy. Efficiency up to 95.5 % (up to 99 % in ECO mode); part of the RED3300-E Series.
- Three-level inverter; efficiency up to 95.5 %, up to 99 % in ECO mode
- Output power factor 1.0; accepts 100 % unbalanced load
- Integrated VRLA battery, up to 6 internal groups — no separate cabinet
- Wide input range 138–485 Vac; input PF ≥ 0.99, THDi ≤ 3 %
- Parallel expansion to 6 units; LBS for dual-bus systems
- Power Walk-In soft start reduces the generator rating required
Overview
The RED3360S-E is the 60 kVA standard (S) model in the RED3300-E Series of three-phase in / three-phase out, true double-conversion online UPS, rated at 380/400/415 Vac for the UK and other IEC markets.
The standard build integrates up to six internal VRLA battery groups in a single 600 mm-wide cabinet, so no separate battery cabinet is needed.
Battery autonomy, string configuration and battery cabinet selection are sized per project — contact us with your load and runtime requirements. Figures are typical values for reference only; specifications are subject to change without prior notice.
- Rated power
- 60 kW
- Input voltage
- 400 V
- Output voltage
- 400 V
- Battery
- VRLA
- Redundancy
- Parallel · N+1
- Market
- United Kingdom · Global
Specifications
Model
- Model code
- RED3360S-E
- Build
- Standard (S) — batteries fitted internally
- Rated power
- 60 kVA / 60 kW
- Dimensions (W × D × H)
- 600 × 1000 × 2000 mm
- Weight
- 950 kg (with batteries)
- Noise
- < 60 dB
- Charging current, max.
- 20 A
Electrical
- Topology
- Online double conversion, DSP control, three-level inverter
- Nominal input / output voltage
- 380/400/415 Vac, 3-phase + N + PE
- Input voltage range
- 138–305 Vac at 40 % load; 305–485 Vac at 100 % load (phase voltage 80–280 Vac)
- Input power factor
- ≥ 0.99
- Input current distortion (THDi)
- ≤ 3 % (linear load)
- Output power factor
- 1.0 (100 % unbalanced load)
- Voltage regulation
- ±1 %
- Output voltage distortion (THDv)
- ≤ 2 % linear load; ≤ 4 % non-linear load
- Output frequency
- Line mode: synchronised with input (50/60 Hz ±0.1 when input exceeds ±10 %); battery mode: 50/60 Hz ±0.2 %
- Crest factor
- 3:1
- Bypass frequency range
- 50/60 Hz ±10 %
- Overload — inverter mode
- ≤ 110 % 60 min; ≤ 125 % 10 min; ≤ 150 % 1 min; > 150 % 1.2 s inverter shutdown
- Overload — bypass mode
- 135 % long term at 30 °C; 125 % long term at 40 °C; > 1000 % for 100 ms
- Efficiency
- AC mode up to 95.5 %; ECO mode up to 99 %
- Parallel
- Up to 6 units, with shared battery option
Battery
- Battery type
- VRLA, internal — up to 6 battery groups
- Battery voltage
- ±240 Vdc (6 × 40 blocks, 12 V 9 Ah)
- Charging current, max.
- 20 A
Environmental
- Operating temperature
- 0–40 °C
- Storage temperature
- −25 to 55 °C (without battery)
- Relative humidity
- 0–95 % (non-condensing)
- Altitude
- < 1000 m ASL; derating required above 1000 m
Communications & features
- Interfaces
- USB, RS-485, RS-232, SNMP and dry-contact card
- Functions
- ECO mode, Power Walk-In soft start, LBS (load bus synchronisation) for dual-bus systems
- Generator
- Generator compatible; Power Walk-In reduces inrush and the generator rating required
Standards
- Safety
- IEC/EN 62040-1, IEC/EN 62477-1
- EMC
- IEC/EN 62040-2 (IEC 61000-2-2, -4-2, -4-3, -4-4, -4-5, -4-6, -4-8, -4-11)
- Performance
- IEC 62040-3:2021, EN IEC 62040-3:2021
Certification & warranty
Certification
Designed and tested to IEC/EN 62040-1 (safety), IEC/EN 62040-2 (EMC), IEC/EN 62040-3 (performance) and IEC/EN 62477-1. EMC certificates of conformity (EMC Directive 2014/30/EU; EN IEC 62040-2:2018, EN 61000-3-12:2011, EN 61000-3-11:2000) cover the 10–20 kVA models (certificate ES201225018E) and the 30–40 kVA models (certificate ES201225020E). Copies are available on request.
Let's Solve Your Power Challenge.
Send an enquiry to our engineering team. We'll help you identify risks and uncover efficiency opportunities.
Renewable Energy & Drives
5325 S Moorland RdNew Berlin, WI 53151United States
Severn Drives & Energy
Units 2 & 3, Kingsley Business ParkNew Road, Kibworth BeauchampLeicestershire, LE8 0LEUnited Kingdom
Send an enquiry
Fill out the form below and we'll be in touch.