BATTERY CABINETS
PureWave BT40-40 Battery Cabinet, 40 × 40 Ah
BT40-4040 × 12 V 40 Ah VRLA · 2 × 20 strings · ± 120 Vdc
- UL 1778
- CSA C22.2 No. 107.3-14
BT40-40
Factory-populated VRLA battery cabinet for PureWave T Series long-run (H) UPS: 40 blocks of 40 Ah on a ± 120 Vdc bus. Cabinets parallel for larger banks, so autonomy is set by cabinet selection rather than site assembly.
- Matched to the PureWave T Series ± 120 Vdc bus
- Two strings of 20 blocks per cabinet
- Cabinets parallel for larger banks
- Quiet operation, below 40 dB
Overview
- Battery
- VRLA
- Market
- United States
Specifications
Battery system
- Battery type
- VRLA (lead-acid, maintenance-free)
- Battery complement
- 40 × 12 V 40 Ah
- Strings
- 2 × 20
- System voltage
- ± 120 Vdc
- Typical recharge time
- 4 hours (to 90 % of full capacity)
- Typical battery life
- 3 – 5 years, depending on discharge cycles and ambient temperature
Physical
- Dimensions W × D × H
- 600 × 850 × 1600 mm
- Weight
- 676 kg
- Noise level
- < 40 dB
Environmental
- Operating environment
- 0 – 40 °C
- Humidity
- 0 – 95 % RH @ 0 – 40 °C, non-condensing
- Altitude
- < 1000 m; derating required between 1000 and 3000 m
Standards
- Safety
- UL 1778 5th Edition, CSA C22.2 No. 107.3-14
Downloads
Datasheets for this model are issued on request. Request documentation.
Certification & warranty
Certification
- UL 1778
- CSA C22.2 No. 107.3-14
GET IN TOUCH
Let's Solve Your Power Challenge.
Send an enquiry to our engineering team. We'll help you identify risks and uncover efficiency opportunities.
North America
Renewable Energy & Drives
5325 S Moorland RdNew Berlin, WI 53151United States
UK & Europe
Severn Drives & Energy
Units 2 & 3, Kingsley Business ParkNew Road, Kibworth BeauchampLeicestershire, LE8 0LEUnited Kingdom
Send an enquiry