STATCOM & STATIC VAR GENERATION

    PureWave DSTATCOM®

    Distributed transmission voltage support
    PureWave DSTATCOM and transformer installed at a wind farm substation, with a turbine behind

    Inverter-based distributed static compensation for transmission systems, delivering leading or lagging VARs in a fraction of a cycle and deployable inside existing substations. Supported with spares, field service and refurbishment, and available to build to order.

    • Reactive current response time of 2 to 4 milliseconds
    • Continuous ratings up to ±10 MVAR in a single container, in increments of ±1.25 MVAR
    • 264% short-term current rating for 2 seconds, ramping to 100% at 4 seconds, or for 3 seconds then stepping to 100%
    • 480 V output connects to systems up to 35 kV through a single step-up transformer
    • Housed in a conventional enclosure or standard ISO container; up to four enclosures can be paralleled
    • Can be deployed in existing substations and can control externally switched capacitor or inductor banks

    Overview

    The PureWave DSTATCOM Distributed Static Compensator is a fast-compensating reactive power source that reduces voltage variations and voltage instability in the transmission system and assists in quick recovery after contingency events. It uses solid-state dc-to-ac inverters coupled to the utility system to create reactive current, supplementing conventional voltage and VAR control devices such as mechanically switched capacitor banks.

    Because it is inverter-based, it provides compensating VARs on a subcycle basis. It can be deployed in existing substations, so compensation can be distributed through the system and projects phased in over a number of years rather than built as one large central asset.

    It is offered with 480 V output that connects to systems up to 35 kV through a single step-up transformer, in a conventional enclosure or a standard ISO container.

    Specifications

    Electrical

    System voltage, continuous output
    480 V to 35 kV, 50 or 60 Hz (single transformation)
    Output voltage
    480 V, connects to systems up to 35 kV using a single step-up transformer
    Continuous rating
    Up to ±10 MVAR in a single container, in increments of ±1.25 MVAR
    Short-term current rating
    264% for 2 seconds, ramping to 100% at 4 seconds; or 264% for 3 seconds, stepping directly to 100%
    Inverter
    IGBT, pulse-width modulated at 4860 Hz
    Efficiency
    > 98% typical

    Performance

    Reactive current response time
    2 to 4 milliseconds
    Compensation
    Leading or lagging VARs on a subcycle basis
    Operating modes
    Voltage control (steady-state or transient) and reactive power output control
    External bank control
    Can control externally switched capacitor or inductor banks

    Control & monitoring

    Operator interface
    PC-based display showing equipment conditions and parameters in real time, with data-logging capability
    Remote monitoring and control
    Via modem connection or DNP 3.0 SCADA interface
    Operation
    Capable of automatic operation without operator intervention; built-in diagnostics

    Cooling & enclosure

    Cooling
    Ambient air cooling
    Temperature range
    -40° to +50° C
    Enclosure options
    Conventional enclosure or standard ISO container; up to four enclosures can be paralleled for higher system output

    Physical (typical pre-packaged ISO-style enclosures)

    5.0 MVAR, 1 container
    40 ft (12.2 m) × 8.0 ft (2.4 m) × 9.5 ft (2.9 m) (L × W × H); 36,000 lb (16,364 kg)
    7.5 MVAR, 1 container
    45 ft (13.7 m) × 8.0 ft (2.4 m) × 9.5 ft (2.9 m) (L × W × H); 48,000 lb (21,818 kg)
    10.0 MVAR, container 1 (lead, 10 MVAR)
    45 ft (13.7 m) × 8.0 ft (2.4 m) × 9.5 ft (2.9 m) (L × W × H); 48,000 lb (21,818 kg)
    10.0 MVAR, container 2 (control)
    20 ft (6.1 m) × 8.0 ft (2.4 m) × 9.5 ft (2.9 m) (L × W × H); 14,000 lb (6,363 kg)
    15.0 MVAR, container 1 (lead and controls, 7.5 MVAR)
    45 ft (13.7 m) × 8.0 ft (2.4 m) × 9.5 ft (2.9 m) (L × W × H); 48,000 lb (21,818 kg)
    15.0 MVAR, container 2 (auxiliary, 7.5 MVAR)
    40 ft (12.2 m) × 8.0 ft (2.4 m) × 9.5 ft (2.9 m) (L × W × H); 36,000 lb (16,364 kg)
    Building footprint, ±10 MVAR with 264% short-time rating
    45 ft × 12 ft building (brochure compares a similarly rated static VAR compensator at nearly 90 ft × 90 ft)
    GET IN TOUCH

    Let's Solve Your Power Challenge.

    Connect with our engineering team for a technical consultation. We'll help you identify risks and uncover efficiency opportunities.

    North America

    Renewable Energy & Drives

    5325 S Moorland RdNew Berlin, WI 53151United States

    UK & Europe

    Severn Drives & Energy

    Units 2 & 3, Kingsley Business ParkNew Road, Kibworth BeauchampLeicestershire, LE8 0LEUnited Kingdom

    Start Your Consultation

    Fill out the form below and we'll be in touch.