PureWave® SMS Storage Management System
Storage management and power conversion platform for renewable integration, energy time-shifting, capacity firming and ancillary services. Documentation and support available from RE&D, and available to build to order.
- Converts ac power to dc to charge the battery and controls discharge into the electrical system
- Eight selectable modes including islanding, peak shaving, frequency regulation and power smoothing
- Automatic islanding on utility over/under-voltage or over/under-frequency events
- Can provide leading or lagging vars
- Controlled locally through an HMI computer or remotely through a SCADA interface
- Supplied in a container with separate inverter room and control room
Overview
The PureWave SMS is a fast-response power controller that converts ac power to dc to charge an energy storage system and controls the discharge of the battery into the electrical system. This lets a wide variety of applications be powered by stored energy when primary power from the utility is not available.
The PCS and batteries are connected in parallel to the distribution feeder through a three-phase transformer. Batteries can be charged during off-peak times and discharged during peak demand, and the system can supply leading or lagging vars. On a utility disturbance it can automatically open the islanding breaker and re-energize the load in voltage-source mode.
Specifications
Operating modes
- Modes
- Islanding, Direct Power Control, Frequency Regulation, Power Smoothing, Power Scheduling, Peak Shaving, Vac Regulation using Vars, Direct Var Control
- System states
- 8: Program Reset, Inhibit, Trip Offline, Ready, Voltage Source Run, Current Source Run, Open Input Switch, Close Input Switch
- Reset types
- Manual, Auto, Self
- Return to utility after disturbance
- Adjustable time delay, 5 minutes default
Control & communications
- Local interface
- HMI industrial PC (Linux operating system) on master control rack
- Remote control
- SCADA interface (DNP points)
- HMI access levels
- Level 1 observe, Level 2 control
- Remote HMI connection
- Electronic certificates only
- Local/Remote switch
- Switches control between SCADA and HMI
- Emergency stop
- INVERTER STOP button, typically at each container man door
Configuration
- Enclosure
- Container with inverter room and control room
- PCS enclosure sections
- Ac section, left and right inverter bays, left and right dc bays
- Inverter bay contents
- Three-phase dc-ac inverter, dc-dc converter (chopper), ac filter inductor
- Dc bay contents
- Two dc circuit breakers and dc interface control panel
- Utility connection
- Through a three-phase transformer
- Cooling
- Fans on ac and dc bays; blower with variable frequency drives on inverter bays
Standards
- Grid protection settings
- Over/under-voltage and over/under-frequency alarms used to comply with IEEE 1547; default settings according to IEEE 1547
Let's Solve Your Power Challenge.
Send an enquiry to our engineering team. We'll help you identify risks and uncover efficiency opportunities.
Renewable Energy & Drives
5325 S Moorland RdNew Berlin, WI 53151United States
Severn Drives & Energy
Units 2 & 3, Kingsley Business ParkNew Road, Kibworth BeauchampLeicestershire, LE8 0LEUnited Kingdom
Send an enquiry
Fill out the form below and we'll be in touch.