PureWave® SMS-250 Power Conversion System
Air-cooled four-quadrant converter for connection to a range of battery types, in a NEMA-3R (IP54) outdoor enclosure. Accommodates 50 Hz and 60 Hz, and systems from 380 to 400 Vac, or to 480 Vac with an auto-transformer.
- 263 kW / 263 kVA power conversion system in a weatherproof NEMA 4 enclosure
- 380 Vac directly, or 400, 415 or 480 Vac using an auto transformer; 50 or 60 Hz
- Designed for a user-furnished 618- to 850-Vdc lithium-ion battery pack
- Modular design capable of parallel operation to double the rating
- Seven operating modes including peak shaving, renewable smoothing and islanding
- Operating range -40°C to 40°C without de-rating
Overview
The PureWave SMS-250 is a 263 kW / 263 kVA power conversion system for battery energy storage. It converts ac power to dc to charge the battery and controls discharge into the electrical system according to the selected power mode.
It connects to a three-phase 50/60 Hz feeder at 380 Vac directly, or at 400, 415 or 480 Vac using an auto transformer, and is housed in a weatherproof enclosure suitable for outdoor or indoor mounting. It is designed for a user-furnished lithium-ion battery pack of 618 to 850 Vdc.
- Rated power
- 263 kW
- Battery
- Lithium-ion
- Redundancy
- Parallel
Specifications
Electrical
- Real/reactive power
- 263 kW / 263 kVA
- Secondary voltage
- 380 Vac directly; 400, 415 or 480 Vac using an auto transformer
- Frequency
- 50 or 60 Hz
- Battery
- User-furnished 618- to 850-Vdc lithium-ion battery pack
- Inverter
- Three-phase, four-quadrant IGBT inverter, pulse-width modulation
- Ac circuit breaker (CB1)
- 400 A
- Dc circuit breaker (CB2)
- 400 A
- Parallel operation
- Modular design capable of parallel operation to double the rating
Physical
- Dimensions (single enclosure)
- 36 W × 36 L × 80 H inches (914 × 914 × 2032 mm)
- Weight
- 2,000 lbs (907.2 kg)
- Enclosure
- NEMA 4, weatherproof, tamper-resistant
- Installation
- Outdoor or indoor, on a concrete or equivalent pad
Environmental
- Ambient operating temperature
- -40°F to 104°F (-40°C to 40°C) without de-rating
- Storage ambient temperature
- -49°F to 140°F (-45°C to 60°C)
- Humidity
- 0% to 100% condensing
- Altitude
- Sea level to 1,000 meters without de-rating
- Seismic
- Uniform Building Code Zone 4
- Audible noise
- < 55 dBA at 3 meters when inverter is not running; < 65 dBA at 3 meters when inverter is running
Control & communications
- Operating modes
- Commanded Control, Frequency Regulation, Islanding, Peak Shaving, Power Scheduling, Renewable Smoothing, Voltage Regulation
- Operating states
- 5: Ready, CS Run, VS Run, Inhibit, Trip Offline
- Control
- SCADA or HMI, selected with the SMS CONTROL switch
- Local display
- Four-line, 40-character LCD
- HMI connection
- Ethernet web server port, accessed with a web browser
- SCADA protocol
- DNP, conforming to DNP V3.00 Subset Definitions; Modbus and DNP register list provided
- Radio
- Provisions for radio communication, 24 Vdc supplied
Standards
- Grid protection
- Over/under-voltage and over/under-frequency alarms used to comply with IEEE 1547
Let's Solve Your Power Challenge.
Send an enquiry to our engineering team. We'll help you identify risks and uncover efficiency opportunities.
Renewable Energy & Drives
5325 S Moorland RdNew Berlin, WI 53151United States
Severn Drives & Energy
Units 2 & 3, Kingsley Business ParkNew Road, Kibworth BeauchampLeicestershire, LE8 0LEUnited Kingdom
Send an enquiry
Fill out the form below and we'll be in touch.