LOW-VOLTAGE MODULAR UPS
PureWave T50H UPS, 50 kVA / 50 kW
T50H50 kVA / 50 kW · 3-phase · 208/120 V · external battery
- UL 1778
- CSA C22.2 No. 107.3-14

Three-phase double-conversion online UPS, 50 kVA with unity output power factor. Long-run unit supplied without batteries, paired with PureWave BT Series battery cabinets sized to the autonomy required.
- True double-conversion online UPS
- Unity output power factor: nameplate kVA is available as kW
- Wide input voltage window with input power factor up to 0.99
- Parallel expandable to six units, with shared-battery operation
- Certified to UL 1778 and CSA C22.2 No. 107.3-14
Overview
- Rated power
- 50 kW
- Input voltage
- 208/120 V · 220/127 V
- Output voltage
- 208/120 V · 220/127 V
- Battery
- VRLA
- Redundancy
- Single unit · Parallel
- Market
- United States
Specifications
Electrical
- Capacity
- 50 kVA / 50 kW
- Configuration
- 3-phase in / 3-phase four-wire out
- Input voltage
- 208/120 or 220/127 Vac (3Ph+N+PE)
- Input operating range
- 66–166 Vac for 40 % load; 96–166 Vac for 100 % load
- Input power factor
- ≥ 0.99
- Input current distortion (THDi)
- ≤ 3 % non-linear load
- Output voltage
- 208/120 or 220/127 Vac (3Ph+N+PE)
- Voltage regulation
- ±1 %
- Output distortion (THDv)
- ≤ 2 % linear load; ≤ 5 % non-linear load
- Crest factor
- 3:1
- Overload
- ≤ 110 % 60 min, ≤ 125 % 10 min, ≤ 150 % 1 min, > 150 % 1.2 s
- Efficiency, double-conversion
- Up to 94 %
- Maximum parallel units
- 6
Battery
- Battery type
- VRLA (lead-acid, maintenance-free)
- Battery voltage
- ± 96 / 108 / 120 / 132 / 144 / 156 Vdc (16–26 pcs; 20 default), external
- Charging current, max.
- 40 A
- Battery cabinet
- PureWave BT Series
Physical
- Dimensions W × D × H
- 442 × 850 × 1200 mm
- Weight
- 160 kg
- Noise level
- < 63 dB
Environmental
- Operating temperature
- 0 – 40 °C
- Storage temperature
- −25 – 55 °C (without battery)
- Humidity
- 0 – 95 % RH @ 0 – 40 °C, non-condensing
- Altitude
- < 1000 m; derating required between 1000 and 3000 m
Standards
- Safety
- UL 1778, CSA C22.2 No. 107.3-14
- EMC
- FCC Part 15 Subpart B, ANSI C63.4-2014
Downloads
Datasheets for this model are issued on request. Request documentation.
Certification & warranty
Certification
- UL 1778
- CSA C22.2 No. 107.3-14
Matched equipment
Battery cabinets, transformers and other equipment used with this product. Confirm the pairing with RE&D before ordering.
GET IN TOUCH
Let's Solve Your Power Challenge.
Send an enquiry to our engineering team. We'll help you identify risks and uncover efficiency opportunities.
North America
Renewable Energy & Drives
5325 S Moorland RdNew Berlin, WI 53151United States
UK & Europe
Severn Drives & Energy
Units 2 & 3, Kingsley Business ParkNew Road, Kibworth BeauchampLeicestershire, LE8 0LEUnited Kingdom
Send an enquiry
Fill out the form below and we'll be in touch.