STATCOM & STATIC VAR GENERATION

    RE&D STATCOM

    1200 – 3600 kvar · 3 – 35 kV · 3-level IGBT

    Modular three-level IGBT STATCOM built from ±600 kvar power modules, up to six per system. Response typically 10–40 ms, fault ride-through to 250 ms, optional active filter across the 2nd–51st harmonic, air or liquid cooled.

    • Modular 3-level IGBT platform built from ±600 kvar power modules, 2 to 6 per system
    • Compensation from 1200 kvar to 3600 kvar at 3 kV – 35 kV with matching transformer
    • Response time application-dependent, typically 10 – 40 ms
    • Faults of up to 250 ms duration do not cause the STATCOM to shut down
    • Losses < 2.1% of compensation maximum, < 1.8% in typical operation, < 0.4% at idle
    • Redundancy at both power module and individual IPU level

    Overview

    RE&D STATCOM provides dynamic capacitive and inductive reactive power compensation for voltage stabilisation, power factor correction and load-flow optimisation in public and industrial medium-voltage distribution networks. It is based on a scalable power electronics platform with 3-level IGBT inverters.

    The platform is built from IGBT power units (125 A, up to 690 V) combined in cabinets to form ±600 kvar power modules. Up to six modules make a complete system of ±3600 kvar, with an integrated control cabinet and circuit breaker, connected to the network through a matching transformer.

    A voltage source converter sources or sinks reactive current continuously and within milliseconds, with no switching steps, no resonance risk with the network, and full rated output retained at reduced network voltage.

    Specifications

    Electrical

    Rated voltage
    3 kV – 35 kV with matching transformer
    Grid frequency
    50 Hz / 60 Hz
    Compensation
    1200 kvar | 1800 kvar | 2400 kvar | 3000 kvar | 3600 kvar
    Number of power modules
    2 | 3 | 4 | 5 | 6 (each ±600 kvar)
    Rated current (690 V)
    1000 A | 1500 A | 2000 A | 2500 A | 3000 A
    IGBT power unit (IPU)
    125 A rated current, up to 690 V rated voltage
    Inverter
    3-level IGBT with voltage intermediate circuit (DC film capacitors)
    Switching frequency
    10 kHz (low-loss design)
    Power loss, active part
    < 2.1% of the compensation maximum; < 1.8% during typical operation; < 0.4% at idle; < 100 W in standby
    Regulating functions
    Voltage regulation; reactive power regulation
    Optional active filter (ACF)
    2nd–51st harmonic (50 Hz) / 2nd–41st harmonic (60 Hz)

    Performance

    Response time
    Application-dependent, typically 10 – 40 ms
    Fault ride-through
    Faults of up to 250 ms duration do not cause the STATCOM to shut down
    Redundancy
    At power module level and at individual IPU level

    Control & interfaces

    Control
    Internal control computer with two digital signal processors
    System setup and display
    HMI with graphical display, or internal web server (TCP/IP) and PC, no additional software required
    Interfaces
    Ethernet (TCP/IP); fieldbus systems including Profibus and Modbus; potential-free configurable digital I/O for status message
    Logging
    Logs saved to SD card for export

    Cooling & enclosure

    Cooling
    Standard: air cooling with variable-speed fans. Optional: liquid cooling with connection to an external cooling system
    IP degree of protection
    Standard: IP20. Optional: IP21 .. IP54
    Colour
    Standard: RAL 7035 light grey (other colours and designs on request)
    Max. ambient temperature without power reduction
    40 °C
    Recommended ambient temperature (continuous operation)
    < 25 °C
    Minimum operating temperature
    0 °C
    Relative humidity
    Maximum 95%
    Transport / storage temperature
    −20 °C .. 70 °C

    Physical

    Power module dimensions (approx. W × D × H)
    800 × 800 × 2000 mm; 800 × 800 × 2200 mm with optional base
    Active part, 1200 kvar (2 modules)
    2200 × 800 × 2000 mm (W × D × H); approx. 1700 kg
    Active part, 1800 kvar (3 modules)
    3000 × 800 × 2000 mm (W × D × H); approx. 2400 kg
    Active part, 2400 kvar (4 modules)
    3800 × 800 × 2000 mm (W × D × H); approx. 3100 kg
    Active part, 3000 kvar (5 modules)
    4600 × 800 × 2000 mm (W × D × H); approx. 3880 kg
    Active part, 3600 kvar (6 modules)
    5400 × 800 × 2000 mm (W × D × H); approx. 4500 kg
    Expandability
    2-winding transformer: up to 6 power modules. 3-winding transformer: up to 2 × 6 power modules (7.2 Mvar)

    Standards

    Designed and built to
    EN 50178, EN 61439-1, EN 61439-2, EN 61000-6-2, EN 61000-6-4, EN 55011
    EMC class
    EN 55011, Class A1 (industrial environment)
    GET IN TOUCH

    Let's Solve Your Power Challenge.

    Connect with our engineering team for a technical consultation. We'll help you identify risks and uncover efficiency opportunities.

    North America

    Renewable Energy & Drives

    5325 S Moorland RdNew Berlin, WI 53151United States

    UK & Europe

    Severn Drives & Energy

    Units 2 & 3, Kingsley Business ParkNew Road, Kibworth BeauchampLeicestershire, LE8 0LEUnited Kingdom

    Start Your Consultation

    Fill out the form below and we'll be in touch.