RE&D STATCOM
Modular three-level IGBT STATCOM built from ±600 kvar power modules, up to six per system. Response typically 10–40 ms, fault ride-through to 250 ms, optional active filter across the 2nd–51st harmonic, air or liquid cooled.
- Modular 3-level IGBT platform built from ±600 kvar power modules, 2 to 6 per system
- Compensation from 1200 kvar to 3600 kvar at 3 kV – 35 kV with matching transformer
- Response time application-dependent, typically 10 – 40 ms
- Faults of up to 250 ms duration do not cause the STATCOM to shut down
- Losses < 2.1% of compensation maximum, < 1.8% in typical operation, < 0.4% at idle
- Redundancy at both power module and individual IPU level
Overview
RE&D STATCOM provides dynamic capacitive and inductive reactive power compensation for voltage stabilisation, power factor correction and load-flow optimisation in public and industrial medium-voltage distribution networks. It is based on a scalable power electronics platform with 3-level IGBT inverters.
The platform is built from IGBT power units (125 A, up to 690 V) combined in cabinets to form ±600 kvar power modules. Up to six modules make a complete system of ±3600 kvar, with an integrated control cabinet and circuit breaker, connected to the network through a matching transformer.
A voltage source converter sources or sinks reactive current continuously and within milliseconds, with no switching steps, no resonance risk with the network, and full rated output retained at reduced network voltage.
Specifications
Electrical
- Rated voltage
- 3 kV – 35 kV with matching transformer
- Grid frequency
- 50 Hz / 60 Hz
- Compensation
- 1200 kvar | 1800 kvar | 2400 kvar | 3000 kvar | 3600 kvar
- Number of power modules
- 2 | 3 | 4 | 5 | 6 (each ±600 kvar)
- Rated current (690 V)
- 1000 A | 1500 A | 2000 A | 2500 A | 3000 A
- IGBT power unit (IPU)
- 125 A rated current, up to 690 V rated voltage
- Inverter
- 3-level IGBT with voltage intermediate circuit (DC film capacitors)
- Switching frequency
- 10 kHz (low-loss design)
- Power loss, active part
- < 2.1% of the compensation maximum; < 1.8% during typical operation; < 0.4% at idle; < 100 W in standby
- Regulating functions
- Voltage regulation; reactive power regulation
- Optional active filter (ACF)
- 2nd–51st harmonic (50 Hz) / 2nd–41st harmonic (60 Hz)
Performance
- Response time
- Application-dependent, typically 10 – 40 ms
- Fault ride-through
- Faults of up to 250 ms duration do not cause the STATCOM to shut down
- Redundancy
- At power module level and at individual IPU level
Control & interfaces
- Control
- Internal control computer with two digital signal processors
- System setup and display
- HMI with graphical display, or internal web server (TCP/IP) and PC, no additional software required
- Interfaces
- Ethernet (TCP/IP); fieldbus systems including Profibus and Modbus; potential-free configurable digital I/O for status message
- Logging
- Logs saved to SD card for export
Cooling & enclosure
- Cooling
- Standard: air cooling with variable-speed fans. Optional: liquid cooling with connection to an external cooling system
- IP degree of protection
- Standard: IP20. Optional: IP21 .. IP54
- Colour
- Standard: RAL 7035 light grey (other colours and designs on request)
- Max. ambient temperature without power reduction
- 40 °C
- Recommended ambient temperature (continuous operation)
- < 25 °C
- Minimum operating temperature
- 0 °C
- Relative humidity
- Maximum 95%
- Transport / storage temperature
- −20 °C .. 70 °C
Physical
- Power module dimensions (approx. W × D × H)
- 800 × 800 × 2000 mm; 800 × 800 × 2200 mm with optional base
- Active part, 1200 kvar (2 modules)
- 2200 × 800 × 2000 mm (W × D × H); approx. 1700 kg
- Active part, 1800 kvar (3 modules)
- 3000 × 800 × 2000 mm (W × D × H); approx. 2400 kg
- Active part, 2400 kvar (4 modules)
- 3800 × 800 × 2000 mm (W × D × H); approx. 3100 kg
- Active part, 3000 kvar (5 modules)
- 4600 × 800 × 2000 mm (W × D × H); approx. 3880 kg
- Active part, 3600 kvar (6 modules)
- 5400 × 800 × 2000 mm (W × D × H); approx. 4500 kg
- Expandability
- 2-winding transformer: up to 6 power modules. 3-winding transformer: up to 2 × 6 power modules (7.2 Mvar)
Standards
- Designed and built to
- EN 50178, EN 61439-1, EN 61439-2, EN 61000-6-2, EN 61000-6-4, EN 55011
- EMC class
- EN 55011, Class A1 (industrial environment)
Let's Solve Your Power Challenge.
Send an enquiry to our engineering team. We'll help you identify risks and uncover efficiency opportunities.
Renewable Energy & Drives
5325 S Moorland RdNew Berlin, WI 53151United States
Severn Drives & Energy
Units 2 & 3, Kingsley Business ParkNew Road, Kibworth BeauchampLeicestershire, LE8 0LEUnited Kingdom
Send an enquiry
Fill out the form below and we'll be in touch.