Low-Voltage Modular UPS

Scalable three-phase modular UPS with dual-DSP digital control. The 50 kW module expands from 50 to 600 kVA/kW in a single cabinet and to 2.4 MW across four in parallel; the 100 kW module reaches 4.8 MW. The power, bypass and control modules are all hot-swappable. Available outdoor-rated and containerized.
- True on-line double conversion with dual-DSP fully digital control
- Output power factor 1.0; on-line efficiency 96 %, up to 99 % in ECO mode
- 50 kW and 100 kW modules scale to 2.4 MW or 4.8 MW with four cabinets in parallel
- Hot-swappable power, bypass and control modules
- Supports lead-acid and lithium iron phosphate batteries, 30-46 cells
- Holds 50 % load with one fan failed and 30 % with two failed
Overview
The Low-Voltage UPS is a new generation of high-end modular UPS systems with three inputs and three outputs. It is a scalable three-phase system with DSP technology, providing true on-line double conversion power protection.
The 50 kW module's power and redundancy can expand vertically from 50 to 600 kVA/600 kW in a single cabinet, and up to four cabinets can operate in parallel, reaching 2.4 MW. The 100 kW module's power and redundancy can expand from 400 to 1200 kVA/kW in one cabinet, with four cabinets in parallel increasing capacity to 4.8 MW.
The modular design allows hot-swappable operation of all modules (power, bypass, and control). The UPS integrates an AC/DC rectifier, a DC/DC converter for the battery pack, and a DC/AC inverter, with bypass and maintenance bypass circuits providing alternative power paths during overload or maintenance.
- Rated power
- 50 kW – 4.8 MW
- Input voltage
- 480 V · 440 V
- Output voltage
- 480 V · 440 V
- Battery
- Lead-acid · Lithium-ion
- Redundancy
- Parallel
Specifications
Electrical
- Topology
- Online double conversion, three-phase, DSP digital control
- Module ratings
- 50 kW and 100 kW
- Single cabinet capacity (50 kW module)
- 50 to 600 kVA/kW
- Single cabinet capacity (100 kW module)
- 400 to 1200 kVA/kW
- Maximum parallel
- Up to four cabinets: 2.4 MW (50 kW module), 4.8 MW (100 kW module)
- Input / output wiring
- 3 Ph + N + PE
- Rated input / output voltage
- 480 / 440 Vac
- Input voltage range
- 384 to 528 Vac (no derating); 288 to 384 Vac (linear derating between 60 % and 100 % load)
- Input frequency range
- 40 to 70 Hz
- Input power factor
- ≥0.99
- Input current distortion
- ≤3 %
- Output power factor
- 1
- Output voltage precision
- ±1 %
- Output voltage distortion
- ≤1 % (resistive load); ≤3 % (non-resistive load)
- Crest factor
- 3:1
- Efficiency
- Online mode 96 %; ECO mode 99 %
- Switching time
- 0 ms
Battery / Energy
- Battery types
- Lead-acid or lithium iron phosphate
- Battery cells
- 30 to 46 cells supported (even number 30 to 46 pcs of 12 V batteries settable)
- Battery voltage
- ±240 Vdc (±180 to ±276 Vdc settable), 40 pcs 12 V batteries
- Battery start
- Can start directly from battery when mains power is unavailable
Overload & protection
- Inverter overload capacity
- 105-110 % load: bypass in 60 min; 110-125 %: 10 min; 125-150 %: 1 min; above 150 %: 200 ms
- Bypass overload capacity
- Load ≤125 % long term; >200 % load for 100 ms
- Protections
- Output short-circuit, output overload, over-temperature, battery low voltage, output over/under voltage, fan failure
- Bypass
- Standard maintenance bypass switch
Physical
- Cabinet dimensions (W x D x H), 200 / 300 kVA models
- 600 × 850 × 2000 mm
- Cabinet dimensions (W x D x H), 400 / 500 kVA models
- 1200 × 850 × 2000 mm
- Cabinet dimensions (W x D x H), 600 kVA model
- 1400 × 850 × 2000 mm
- Cabinet net weight (200 / 300 / 400 / 500 / 600 kVA)
- 230 / 240 / 410 / 450 / 600 kg
- Module dimensions (W x D x H)
- 440 × 620 × 130 mm
- Module net weight
- 32 kg
- Footprint
- 300 kVA system occupies 0.5 m²
- Color
- Black
Environmental
- Operating temperature
- 0 to 40 °C
- Storage temperature
- -25 to 55 °C (without battery)
- Relative humidity
- 0 to 95 % (non-condensing)
- Altitude
- ≤1000 m; above 1000 m derate 1 % for each additional 100 m
- Protection level
- IP20
- Noise at 1 m
- ≤65 dB (200 / 300 kVA models); ≤68 dB (400 / 500 / 600 kVA models)
Control & communications
- Display
- 7-inch LCD touch screen
- Standard interfaces
- RS485, RS485/CAN (BMS), NET (with SNMP function), input/output dry contacts, EPO
- Optional
- Parallel kits, LBS components, WiFi card, 4G card, battery temperature sensor, EMD environment detector
- Frequency conversion
- 50 Hz to 60 Hz supported
Let's Solve Your Power Challenge.
Send an enquiry to our engineering team. We'll help you identify risks and uncover efficiency opportunities.
Renewable Energy & Drives
5325 S Moorland RdNew Berlin, WI 53151United States
Severn Drives & Energy
Units 2 & 3, Kingsley Business ParkNew Road, Kibworth BeauchampLeicestershire, LE8 0LEUnited Kingdom
Send an enquiry
Fill out the form below and we'll be in touch.