UPS SYSTEMS

    Low-Voltage Modular UPS

    50 kW – 4.8 MW · three-in / three-out · LV

    Scalable three-phase modular UPS with dual-DSP digital control. The 50 kW module expands from 50 to 600 kVA/kW in a single cabinet and to 2.4 MW across four in parallel; the 100 kW module reaches 4.8 MW. The power, bypass and control modules are all hot-swappable. Available outdoor-rated and containerized.

    • True on-line double conversion with dual-DSP fully digital control
    • Output power factor 1.0; on-line efficiency 96 %, up to 99 % in ECO mode
    • 50 kW and 100 kW modules scale to 2.4 MW or 4.8 MW with four cabinets in parallel
    • Hot-swappable power, bypass and control modules
    • Supports lead-acid and lithium iron phosphate batteries, 30-46 cells
    • Holds 50 % load with one fan failed and 30 % with two failed

    Overview

    The Low-Voltage UPS is a new generation of high-end modular UPS systems with three inputs and three outputs. It is a scalable three-phase system with DSP technology, providing true on-line double conversion power protection.

    The 50 kW module's power and redundancy can expand vertically from 50 to 600 kVA/600 kW in a single cabinet, and up to four cabinets can operate in parallel, reaching 2.4 MW. The 100 kW module's power and redundancy can expand from 400 to 1200 kVA/kW in one cabinet, with four cabinets in parallel increasing capacity to 4.8 MW.

    The modular design allows hot-swappable operation of all modules (power, bypass, and control). The UPS integrates an AC/DC rectifier, a DC/DC converter for the battery pack, and a DC/AC inverter, with bypass and maintenance bypass circuits providing alternative power paths during overload or maintenance.

    Rated power
    50 kW – 4.8 MW
    Input voltage
    480 V · 440 V
    Output voltage
    480 V · 440 V
    Battery
    Lead-acid · Lithium-ion
    Redundancy
    Parallel

    Specifications

    Electrical

    Topology
    Online double conversion, three-phase, DSP digital control
    Module ratings
    50 kW and 100 kW
    Single cabinet capacity (50 kW module)
    50 to 600 kVA/kW
    Single cabinet capacity (100 kW module)
    400 to 1200 kVA/kW
    Maximum parallel
    Up to four cabinets: 2.4 MW (50 kW module), 4.8 MW (100 kW module)
    Input / output wiring
    3 Ph + N + PE
    Rated input / output voltage
    480 / 440 Vac
    Input voltage range
    384 to 528 Vac (no derating); 288 to 384 Vac (linear derating between 60 % and 100 % load)
    Input frequency range
    40 to 70 Hz
    Input power factor
    ≥0.99
    Input current distortion
    ≤3 %
    Output power factor
    1
    Output voltage precision
    ±1 %
    Output voltage distortion
    ≤1 % (resistive load); ≤3 % (non-resistive load)
    Crest factor
    3:1
    Efficiency
    Online mode 96 %; ECO mode 99 %
    Switching time
    0 ms

    Battery / Energy

    Battery types
    Lead-acid or lithium iron phosphate
    Battery cells
    30 to 46 cells supported (even number 30 to 46 pcs of 12 V batteries settable)
    Battery voltage
    ±240 Vdc (±180 to ±276 Vdc settable), 40 pcs 12 V batteries
    Battery start
    Can start directly from battery when mains power is unavailable

    Overload & protection

    Inverter overload capacity
    105-110 % load: bypass in 60 min; 110-125 %: 10 min; 125-150 %: 1 min; above 150 %: 200 ms
    Bypass overload capacity
    Load ≤125 % long term; >200 % load for 100 ms
    Protections
    Output short-circuit, output overload, over-temperature, battery low voltage, output over/under voltage, fan failure
    Bypass
    Standard maintenance bypass switch

    Physical

    Cabinet dimensions (W x D x H), 200 / 300 kVA models
    600 × 850 × 2000 mm
    Cabinet dimensions (W x D x H), 400 / 500 kVA models
    1200 × 850 × 2000 mm
    Cabinet dimensions (W x D x H), 600 kVA model
    1400 × 850 × 2000 mm
    Cabinet net weight (200 / 300 / 400 / 500 / 600 kVA)
    230 / 240 / 410 / 450 / 600 kg
    Module dimensions (W x D x H)
    440 × 620 × 130 mm
    Module net weight
    32 kg
    Footprint
    300 kVA system occupies 0.5 m²
    Color
    Black

    Environmental

    Operating temperature
    0 to 40 °C
    Storage temperature
    -25 to 55 °C (without battery)
    Relative humidity
    0 to 95 % (non-condensing)
    Altitude
    ≤1000 m; above 1000 m derate 1 % for each additional 100 m
    Protection level
    IP20
    Noise at 1 m
    ≤65 dB (200 / 300 kVA models); ≤68 dB (400 / 500 / 600 kVA models)

    Control & communications

    Display
    7-inch LCD touch screen
    Standard interfaces
    RS485, RS485/CAN (BMS), NET (with SNMP function), input/output dry contacts, EPO
    Optional
    Parallel kits, LBS components, WiFi card, 4G card, battery temperature sensor, EMD environment detector
    Frequency conversion
    50 Hz to 60 Hz supported
    GET IN TOUCH

    Let's Solve Your Power Challenge.

    Connect with our engineering team for a technical consultation. We'll help you identify risks and uncover efficiency opportunities.

    North America

    Renewable Energy & Drives

    5325 S Moorland RdNew Berlin, WI 53151United States

    UK & Europe

    Severn Drives & Energy

    Units 2 & 3, Kingsley Business ParkNew Road, Kibworth BeauchampLeicestershire, LE8 0LEUnited Kingdom

    Start Your Consultation

    Fill out the form below and we'll be in touch.